FASTEL KableFree is the UK’s first radio monitoring self-testing emergency lighting system that uses proven FASTEL technology to deliver total peace of mind with operational cost savings
Digital processing
Fully automatic self-testing – communicates back to LAN based MWeb KFR
6-year battery warranty on all FASTEL KFR equipped emergency luminaires
Minimum disruption during installation. Considerable cost savings in time and materials
Ideal for historic or heritage buildings where wiring channels are detrimental to the fabric of the building
A microprocessor contained within the FASTEL invertor automatically self tests the emergency lighting in excess of the requirements of BS 5266.
48 hours after the mains is connected to the unit a 3 hour full duration commissioning test is carried out, checking both lamp and battery capacity followed by battery training to preset deep discharge protection point.
8 days later a short test checks both lamp and battery.
8 days later a short test checks both lamp and battery.
8 days later a short test checks both lamp and battery.
8 days later a 3 hour full duration test checks both lamp and battery capacity followed by battery training.
8 days later a short test checks both lamp and battery, ad infinitum.
The above cycle of three short tests and one full test is carried out on a 32 day cycle until the mains supply to the unit is interrupted. Once the supply is reconnected the testing cycle will start 48 hrs after connection, with a full duration commissioning test.
A test cannot be carried out within 48 hours of a previous test or of a mains failure exceeding 5 minutes.
To ensure that adjacent units do not test simultaneously, all test are randomly timed, plus/minus 12 hours, and are additionally randomly timed via battery capacity.
LED INDICATION
Green flashing - for 48 hours, prior to commissioning of following full duration tests
Solid green - System healthy, or self testing if lamp illuminated in test mode.
Flashing Red plus *sounder - Battery capacity or connection fault
Flashing Red (interrupted) plus *sounder - Lamp fault
LED extinguished - Mains failure / disconnection or faulty inverter.
* Sounder operates for 10 seconds every hour until the fault is rectified.